PDF 原檔:報告_OCP2026_Siemens_Skeleton_600kW_800VDC_Sidecar_20261015_original.pdf
講者公開簡報(OCP 官方 Recorded Content 頁提供下載)。文字以 PyMuPDF 逐頁抽取,
### p<n>為頁碼;圖表內容見原檔。
圖片清單(已驗證 2026-10-19)
| 檔名 | 頁 | 分類 | 親眼所見內容 |
|---|---|---|---|
報告_OCP2026_Siemens_Skeleton_600kW_800VDC_Sidecar_20261015_p3.png |
p3 | 真資料圖 | 機櫃功率長條圖:Gen1 GB200/GB300 145kW、Gen2 Vera Rubin NVL72 330kW、Gen3 液冷 570kW、Gen4 原生 800VDC 1,000kW,右側 Graphene Sidecar 1,200kW |
報告_OCP2026_Siemens_Skeleton_600kW_800VDC_Sidecar_20261015_p5.png |
p5 | 真資料圖 | GrapheneSidecar 方塊圖:三相 AC 配電到 AC/DC 轉換、Protection、Power smoothing,輸出 Safe 800VDC 進 IT 機櫃內 DC/DC,再輸出 50VDC 給 IT 負載 |
報告_OCP2026_Siemens_Skeleton_600kW_800VDC_Sidecar_20261015_p7.png |
p7 | 真資料圖 | 實驗室量測曲線:負載到 PSU 電流衰減對頻率(約 0.1Hz 至 1kHz 以上),低頻衰減約 -70dB、隨頻率上升遞減,文字標示 0.1-55Hz 次諧波需衰減 |
報告_OCP2026_Siemens_Skeleton_600kW_800VDC_Sidecar_20261015_p8.png |
p8 | 真資料圖 | 48OU 機櫃配置圖與實物:DC PDU(3 路 DC OUT 2x250A)、PSU800 與 CBU800 交替,共 4 組 PSU800、4 組 CBU800、2 組 DC PDU,底部 CDU,寬 600mm;附 Siemens SSCB 與 Skeleton 機箱外觀 |
報告_OCP2026_Siemens_Skeleton_600kW_800VDC_Sidecar_20261015_p9.png |
p9 | 真資料圖 | Skeleton CBU800 模組實物照與冷卻水路 3D 圖,圓柱超級電容排列於模組內,一側為電力電子與水冷接頭 |
原始內容
p1
Guang Yang Director of R&D at Siemens Industry US Tero Järveläinen CPO at Skeleton Technologies From Principles to Practice: Implementing OCP LVDC Frameworks with a 600kW, 800VDC Sidecar Power System Design RACK & POWER
p2
High-power AI racks require both rapid peak-power support and fast fault protection, but today’s solutions typically treat them as separate challenges. We’re proposing a first-of-its-kind sidecar solution that combines solid-state circuit protection and high-power storage technology for peak power management performance.
p3
"We are now a power-limited industry." Jensen Huang, GTC 2025 keynote NVIDIA, 800 VDC Architecture: Industry Alignment & Execution, 2026 GPU - Graphical Processing Unit Rack power grew 7× in four generations. The rack didn't. NVLink requires GPUs to sit physically close to act as one synchronous accelerator. Copper reach sets the distance; density follows. Power delivery has stopped being a supporting function and become a primary constraint on scalability. 145 kW 330 kW 570 kW 1,000 kW 1,200 kW 0 kW 250 kW 500 kW 750 kW 1,000 kW Gen 1 GB200/GB300 Gen 2 Vera Rubin NVL72 Gen 3 liquid-cooled Gen 4 native 800 VDC Graphene Sidecar
p4
GrapheneSidecar leverages Benefits of 800 VDC without Upstream Electrical Infrastructure Changes Power infrastructure evolution. GrapheneSidecar implements the AC-to- 800VDC conversion, potentially feeding multiple IT racks. Original image source [1] • GrapheneSidecar connects to the existing AC distribution and provides protected 800 VDC output. • GrapheneSidecar provides active peak shaving and load smoothing to ensure AC input power is smooth, • GrapheneSidecar integrates backup on 800VDC side. [1] J. Adrian, M. Tu, Powering the Next Era of AI: How Google, Microsoft and Nvidia Are Standardizing and Accelerating the Industry Transition to LVDC, OpenCompute blog
p5
GrapheneSidecar leverages Benefits of 800 VDC without Upstream Electrical Infrastructure Changes Concentrating the power conversion equipment in the sidecar enables increased compute density in the IT rack. GrapheneSidecar implements AC/DC conversion from three-phase AC to 800 VDC, power smoothing, and fast fault protection of the 800 VDC output. The sidecar is compatible with both the “50V server” and the “Next gen 800V native server” architectures as described in [1]. [1] Data Center Facility – Low voltage direct current power distribution. OpenCompute, 3/2026. OpenCompute whitepaper
p6
GrapheneSidecar enables the integration of Load Smoothing Near the Load Measurements by Skeleton Technologies, load profiles influenced by NVIDIA generic profiles presented in [1]. Load smoothing (or Peak shaving) is essential to avoid grid power fluctuations at subharmonic frequencies that can cause oscillations, grid instability, or even blackout. Utilizing electrical double-layer capacitors (EDLCs) gives high power density allowing to lower the minimum power floor (MPF) of the GPUs, which reduces energy consumption and GPU wear. With load smoothing No load smoothing With load smoothing No load smoothing [1] R. Dimitrov, H. Petty, N. Srivastava, M. Blake, “How New GB300 NVK72 Features Provide Steady Power for AI”, NVIDIA Technical Blog, 6/2025, Available online
p7
Results: Very high attenuation across wide frequency range Subharmonic components in the range 0.1 – 55 Hz are important to attenuate to maintain grid stability. Filtering the subharmonics in the sidecar, close to the loads, is the best possible location as the whole upstream sees a fluctuation-free power demand. Laboratory test results Load to PSU Current Attenuation as a Function of Frequency PSU - Power Supply Unit
p8
GrapheneSidecar delivers Superior Power Density Liquid cooling allows packing 1.2 MW of power into a 48OU cabinet. PSU is 3OU high and delivers 300 kW continuous power. It implements isolation and allows bidirectional power flow for applications like utility grid support with the CBU/BBU energy. Load smoothing is implemented with a capacitor bank unit (CBU) each providing 160 kW of continuous power and 240 kW peak. Solid-state circuit breaker (SSCB) are designed to form factors that are better fit in cabinet formats. They are implemented to ensure reliable protection to faults at all current levels and to protect against arc flash and capacitor discharge 48 Network switch 47 System controller + misc 46 DC OUT (2x250A) 45 44 DC PDU DC OUT (2x250A) 43 42 DC OUT (2x250A) 41 AC IN (3x125A) 40 AC IN (3x125A) 39 PSU800 AC IN (3x125A) 38 37 36 CBU800 35 34 AC IN (3x125A) 33 AC IN (3x125A) 32 PSU800 AC IN (3x125A) 31 30 29 CBU800 28 27 26 Free 25 24 DC OUT (2x250A) 23 22 DC PDU DC OUT (2x250A) 21 20 DC OUT (2x250A) 19 AC IN (3x125A) 18 AC IN (3x125A) 17 PSU800 AC IN (3x125A) 16 15 14 CBU800 13 12 AC IN (3x125A) 11 AC IN (3x125A) 10 PSU800 AC IN (3x125A) 9 8 7 CBU800 6 5 4 3 CDU 2 1 600 mm BBU – Battery Backup Unit Representative picture. UL version to be released
p9
GrapheneSidecar delivers Superior Power Density with Liquid Cooling Liquid cooling allows direct conduction of heat away from the hotspots and enables the use of smaller, more power-dense semiconductor switches and magnetic components and packing the energy storage efficiently. Currently, the power infrastructure is almost exclusively air-cooled, but as the power density grows, the liquid cooling infrastructure that is already available for the GPUs is likely to be extended to the power components. Skeleton CBU800 module (bottom) and its cooling circuit (top). Power electronics (delivering 80 kW continuous power and 120 kW peak) occupies 10-15 % of the volume – the remaining space is filled with supercapacitors.
p10
GrapheneSidecar is built With Flexibility in Mind The GrapheneSidecar components allow building different kinds of sidecars. GrapheneSidecar AC suits perfectly to existing installations where load smoothing needs to be implemented without modifying the IT racks. GrapheneSidecar DC is future-ready for 800-VDC distribution in the data hall. Left: GrapheneSidecar AC leaves out the DC PDU. It can be used as an AC-connected load smoothing unit or a single-conversion UPS. Right: GrapheneSidecar DC leaves out the AC/DC conversion and can connect directly to 800-VDC distribution implementing load smoothing or battery backup. Both designs utilize the same building blocks presented earlier.
p11
A power sidecar is not just a relocated power shelf What moves out of the IT rack Backup BBUs giving 80 kW for 60 seconds Conversion 415–480 VAC in over 12× 100A whips, out as 800 VDC via 6× 18.3 kW PSU shelves Redundancy N+N feed configurations that no longer fit in the compute rack Interface Up to 250A interlocked DC whips, de-energized on mate and unmate What the sidecar must add Sub-second energy storage slew rate control, input current shaping, smoothing and fault holdup, spanning microseconds to roughly one second Fault current limiting current limiting on every fault-contributing source, capacitors included, because DC arc flash methodology depends on it Protection zoning residual current monitoring using Solid State Circuit Breaker as fault energy grows The sidecar has to make a 600 kW rack look stable and predictable and that is a control and energy storage problem.
p12
Get ready for the next-generation of rack level power architecture CALL TO ACTION 1. Help define power smoothing and protection requirements for 800 VDC Join the Power Distribution sub-project and contribute to its LVDC workstreams. 2. Build on the Diablo sidecar specification Extend the open sidecar architecture with standard interfaces for energy storage, load smoothing and solid-state protection. 3. Share benchmark load profiles Common test profiles and attenuation targets, especially for the 0.1–55 Hz sub- harmonic band, will let the industry compare solutions on equal terms. • As rack power approaches 1 MW, power smoothing and fault protection can no longer be treated as separate functions. • The industry needs scalable architectures that maintain stability, safety, and serviceability in 800 VDC environments. • Combining solid-state circuit breakers for fast protection with high-power storage for peak load mitigation.
p13