Stock LLM Wiki

報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015

PDF 原檔:報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_original.pdf

講者公開簡報(OCP 官方 Recorded Content 頁提供下載)。文字以 PyMuPDF 逐頁抽取,### p<n> 為頁碼;圖表內容見原檔。

圖片清單(已驗證 2026-10-19)

檔名 頁 分類 親眼所見內容
報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_p3.png p3 真資料圖 XPO 產品結構總覽:高速連接器、電源連接器、cage、液冷與纜線組件爆炸圖;插拔模組內含上下 Paddle Card A/B、中間 Integrated Cold Plate(Liquid Inlet/Outlet)、MPO Connectors、Latching Mechanism
報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_p4.png p4 真資料圖 1 個 XPO 模組 vs 8 個 OSFP 模組並排實體圖;標註 XPO 高速訊號 C/L pitch 0.56mm、OSFP 0.60mm;224G 12.8 Tbps、448G 25.6 Tbps;8 組 OSFP Sideband/Vcc 合併為 1 片電源與邊帶 PCB
報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_p5.png p5 真資料圖 面板密度比較:1OU 交換器 128 個 XPO 埠 vs 2RU 交換器 64 個 OSFP 埠;8 OSFP 約 190mm x 16.5mm、1 XPO 約 60.79mm x 21.10mm;註記 128 埠 1OU 實作仍在審慎評估
報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_p11.png p11 真資料圖 冷板熱模擬:1x2 並聯、200W,外/內溫度分布最高 64.49°C;備註壓降 34.63 kPa(5.02 PSI)、36.44 kPa(5.29 PSI),最大流量標示 0.4L/min,規格 >5PSI、<70°C
報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_p13.png p13 真資料圖 OFC 2026 XPO 現場展示照與 VNA 量測曲線(10MHz~67GHz,53.125GHz 標記 -3.93dB);治具 -6.63dB、300mm 回路纜線 -3dB;去嵌後單一連接器介面 -0.465dB
報告_OCP2026_FIT鴻騰_XPO液冷光互連架構_20261015_p18.png p18 真資料圖 448G XPO vs 224G XPO 差分插損模擬曲線(0~130GHz):80GHz 處 448G -0.89dB、224G -1.32dB;224G 在約 90GHz 後急降;448G 在 112GHz 約 -2dB;標示 PAM6 89.6GHz/PAM4 112GHz 兩條紅線

原始內容

p1

Terry Little Sr. Development Engineering Manager Foxconn Interconnect Technology XPO (eXtra Dense Pluggable Optics): A High-Density, Liquid-Cooled Optical Interconnect Architecture for Next- Generation AI Networks [PHOTONICS TRACK]

p2

XPO (eXtra-dense Pluggable Optics) Introduction Today, we are proud to introduce our XPO (eXtra-dense Pluggable Optics) platform—a fully integrated, high-density “pluggable” connectivity architecture. We will discuss a scalable path forward from today’s 224 Gbps solutions, to the next-generation 448 Gbps AI and high- performance computing systems. I would like to acknowledge the leadership and vision of Andy Bechtolsheim, Co-founder and Chief Architect of Arista Networks, and the contributions of the XPO MSA member companies in advancing the next generation of high-density optical interconnect technology. Key highlights include: • High-density “Card-edge” connector for next-generation AI infrastructure, both for 224 Gbps, and keeping the same existing XPO connector form factor as we progress towards 448 Gbps.. • Builds upon the proven 224 Gbps architecture to provide a scalable path to 448 Gbs. • “XPO is more than a connector—it is a complete platform engineered to deliver greater bandwidth, improved cooling, and higher system efficiency.”

p3

XPO HS Connector, Power Connector, Cage and Plug Module Product XPO High Density Pluggable Connector, Cage, Liquid Cooling and Cable Assembly XPO Host Connector Architecture XPO Host Liquid Cooling Architecture XPO Host Plug Module Architecture

p4

The XPO architecture consolidates the full connectivity of eight individual OSFP plug modules including high-speed signals, power, and sideband communications—into one compact XPO plug module • The same bandwidth of 8 OSFP modules is consolidated into 1 XPO module • For 224 Gbps signaling: delivers up to 12.8 Tbps per XPO plug module • For future 448 Gbps signaling: will deliver up to 25.6 Tbps per XPO plug module • Integrates high-speed data, power, sidebands, and liquid cooling • Delivers significantly greater bandwidth density in a compact footprint • Reduces front-panel space and simplifies system integration XPO increased density per Plug Module 1 XPO Plug Module has the same HS signal bandwidth, power and sidebands as 8 OSFP Plug Modules. OSFP C/L pitch for HS signals is 0.60mm 1 XPO Plug Module XPO C/L pitch for HS signals is 0.56mm OSFP Module XPO Module ````` Equivalent of 8 OSFP Sidebands and Vcc. Contact Groups Combined into 1 Compact XPO Power and Sideband PCB

p5

The XPO architecture delivers a major improvement in front-panel density compared with conventional OSFP solutions. • A single compact XPO module consolidates the connectivity and bandwidth of eight OSFP ports. • Eight OSFP ports require approximately 190 mm × 16.5 mm of front-panel space. • One XPO module occupies only approximately 60.79 mm × 21.10 mm, significantly reducing the required panel width. • On a rack-unit basis, XPO provides approximately 4× greater port density. • XPO enables higher total switch bandwidth in a smaller enclosure, making it well suited for next-generation AI, HPC, and hyperscale data-center systems. XPO increased density per Front Panel Real Estate Vertical Spaces are occupied by OSFP Cold Plates or Riding Heat-sinks Liquid Cooling Cold Plates are integrated into the XPO Plug Modules which provide a significant reduction in “Z” height NOTE: A potential 128-port XPO implementation in a 1OU switch is being carefully considered, paying close attention to the mechanical, thermal, and routing design requirements associated with the limited available space.

p6

XPO Power Board (PWB) Plug Module Side 1. This side mates to the FIRST SIDE of the Power Connector inside XPO Main Connector body. 2. Mezzanine Connectors provide Power and S.B. control to XPO Paddle Cards. XPO Power Board (PWB) Host Side 1. This side accommodates a Power Cable which will attach to the customer’s IO board inside the system. 2. This side mates to the SECOND SIDE Power Connector inside XPO Main Connector body. XPO Power Board Assembly – Module and Host Side 1.57mm thick PWB (Host Side) 1.0mm thick PWB (Module Side) 1st Side - “Pass-Thru” Power Connector – 2nd Side

p7

Mezzanine Connectors 2 Mated Pairs Per PLUG MODULE Assembly 1. Mezzanine Connectors provide Power and S.B. control to XPO Paddle Cards. XPO Power Board Assembly – Module and Host Side (cont.)

p8

• XPO is designed as an optical-technology-independent platform that can support LPO, LRO, DSP-based and retimed modules, as well as emerging silicon-photonics. • XPO accommodates multimode and single-mode optical technologies. • XPO enables applications ranging from short-reach intra-rack links to longer- reach data-center interconnects. • XPO provides a common electrical and mechanical platform for multiple optical suppliers and evolving standards. • XPO protects the system investment by allowing future optical technologies to be adopted without replacing the entire switch. • The versatile Optical technology is in the Plug Module, outside of the switch. XPO “Pluggable Optics” versatility

p9

XPO Cabled Assembly Exploded View – Total 128 DP (64 Tx / 64 Rx) One wafer Housing Eight wafers XPO Cabled assembly XPO Cabled Connector Assembly Summary: • The XPO connector provides 128 differential pairs (DP): 64 transmit (Tx) and 64 receive (Rx). • Each cable wafer contains a portion of the high- speed signal connections. • Eight wafers are stacked and integrated into a single compact connector housing. • The housing aligns, protects, and mechanically secures the wafer stack. • The final XPO cabled assembly combines all eight wafers into one high-density interface, delivering the equivalent high-speed connectivity of eight OSFP plug modules in a much smaller form factor.

p10

XPO “Direct Wire Attach” Connector This slide illustrates how ultra-fine 30 and 32-AWG drainless twin-ax cable enables the XPO connector’s extremely high-speed signal integrity existing 224G and future 448G-per-lane performance. • The 0.56 mm conductor spacing allows for many differential pairs to be tightly arranged within each XPO wafer. • The 92 Ω controlled-impedance design supports a stable, low-reflection high-speed transmission path. • The drainless raw cable construction eliminates conventional drain wires, reducing cable size and simplifying dense termination. • Metal-foil shielding with full coverage helps control EMI and pair-to-pair crosstalk. • The anticipated insertion-loss targets through 112 GHz indicate that the raw cable is engineered for next-generation 448G signaling.

p11

XPO Cold Plate Thermal Simulation Notes: 1x2 Design – Parallel Configuration – 200W 1. The pressure drop is 34.63 kPa (5.02 PSI) at Maximum flow rate 0.4L/min,can meet spec(>5PSI). 2. The pressure drop is 36.44 kPa (5.29 PSI) at Maximum flow rate 0.4L/min,can meet spec(>5PSI). 3. The max temperature of Module is 64.49℃,can meet spec(<70℃). Outside temperature contours Inside temperature contours

p12

Item` Description Analysis Type Static Structural Analysis Material Copper, C10200, Soft Material Yield Strength 49.8 MPa Loading Condition 200 psi pressure applied on all internal flow channel walls Evaluation Criteria Total Deformation & Equivalent (Von-Mises) Stress XPO Cold Plate Mechanical Burst Pressure Simulation Maximum von-Mises stress 30.87 Mpa Maximum deformation 1.136 μm

p13

FIT XPO 224 Gbps High Speed Test Data – OFC 2026 XPO Live Demo After De-embedding the Test Fixture, the TRUE TEST DATA WITH LOOPBACK CABLE shows -3.93 dB IL minus the 3.0 dB for Raw Loopback Cable which is -0.93 dB. Then divide by 2 for the 2 connector interfaces – (Top and Bottom) which results as -0.465 dB IL.

p14

TX 60 TX 54 TX 52 TX 56 TX 59 TX 63 TX 51 TX 55 Pre FEC BER 5.28E-12 2.77E-12 1.07 E-12 3.50E-11 7.25E-10 7.31E-11 2.65E-10 2.67E-10 Post FEC BER 0 0 0 0 0 0 0 0 EXFO BA-1600 Wilder Tec XPO 224G HCB (128DP) FIT XPO 224 Gbps Connector Loop-back BER Test– 8 Differential Pairs

p15

Fast-forward to 448 Gbps XPO

p16

XPO “Fast-forward” to 448 Gbps Traditional 224G “Cantilever Beam” Contact Geometry Objectives The mechanical objective is to maintain the same XPO “Card-Edge” Form Factor. (0.56mm Pitch) The electrical objective is to minimize undesirable stub effects at high frequencies. High-speed interfaces are sensitive to: •Stub length •Impedance discontinuities •Reflection-induced insertion loss • Traditional “Cantilever Beam Contact Geometry produces un-desirable IL “roll-off” at high frequency. • The New 448G XPO system connector delivers optimization for: • Improved Electrical Performance • Reduced stub length • Improved insertion loss performance • Enhanced high-frequency signal integrity

p17

XPO Card-edge 448G Simulation Results--Differential Impedance Cable Cable Solder AIC Mating Mating Mating impedance mating Cable solder 224G 81.93Ω 85.04Ω 448G 89.00Ω 92.00Ω 224G XPO 448G XPO

p18

Diff5/11 Diff6/12 Diff1/7 Diff2/8 Diff3/9 Diff4/10 Assuming 448 Gb/s per electrical lane and ignoring FEC/encoding overhead: For a practical PAM6 implementation using 5 bits encoded across 2 PAM6 symbols—2.5 bits/symbol: • Symbol rate: 448 ÷ 2.5 = 179.2 GBd • Nyquist frequency: 179.2 ÷ 2 = 89.6 GHz So, the anticipated targets are approximately: • 448G PAM4: 112 GHz • 448G PAM6: 87–90 GHz • Actual baud rate and Nyquist frequency will be slightly higher when line-coding or FEC overhead is included. XPO Card-edge 448G Simulation Results--Differential Insertion Loss 224G XPO 448G XPO

p19

Diff5/11 Diff6/12 Diff1/7 Diff2/8 Diff3/9 Diff4/10 XPO Card-edge 448G Simulation Results--Differential Return Loss 224G XPO 448G XPO Assuming 448 Gb/s per electrical lane and ignoring FEC/encoding overhead: For a practical PAM6 implementation using 5 bits encoded across 2 PAM6 symbols—2.5 bits/symbol: • Symbol rate: 448 ÷ 2.5 = 179.2 GBd • Nyquist frequency: 179.2 ÷ 2 = 89.6 GHz So, the anticipated targets are approximately: • 448G PAM4: 112 GHz • 448G PAM6: 87–90 GHz • Actual baud rate and Nyquist frequency will be slightly higher when line-coding or FEC overhead is included.

p20

448G XPO Path-forward is critical 448G solutions are needed to support both PAM-6 and PAM-4 modulations Additional information: XPO MSA | https://xpomsa.com/ IEEE 802.3dv | https://www.ieee802.org/3/dv/ FIT | https://www.fit-foxconn.com/ Call to Action

p21

Thank You!