報告_OCP2026_ABB_Eaton_主題演講_資料中心直流配電_20261015_p3.png p3 真資料圖 AI 機櫃功率長條圖:2023 50kW、2024 120kW、2025 140kW、2026 240kW、2027 600kW、2028 1.2MW,2029 為斜線預留柱
報告_OCP2026_ABB_Eaton_主題演講_資料中心直流配電_20261015_p5.png p5 真資料圖 DC 供電架構:電網 34.5kVac→固態變壓器 MVAC/800Vdc→主配電 800Vdc→本地配電至機櫃(800Vdc 或 +/-400Vdc),機櫃頂部各有 DC/DC 接 IT

原始內容

p1

Shifting to DC Power Distribution in Data Centers: A Collaborative Journey Paolo Catapane Peter de Bock

p2

(本頁無可抽取文字,內容在圖中)

p3

AI RACK DENSITY • Scale-up requires tightly coupled compute • Power, cooling and networking compete for space • Low-voltage AC faces current, copper, heat, and space limits 120 140 240 600

p4

MORE COMPUTE The Shift DC • Fewer conversions • Higher power density • Smaller footprint 800 V • At same power 16× less current 256× less power losses Less copper Less heat

p5

How do we enable DC ? ..an architecture is needed SOLID STATE TRANSFORMER MVAC/800Vdc LOCAL DISTRIBUTION TO RACKS MAIN POWER DISTRIBUTION 800Vdc 800Vdc, +/- 400Vdc GRID 34.5kVac

p6

If you want to go far, go together

p7

Hyperscalers & cloud providers Semiconductor Manufacturers Electrical Infrastructure OEMs Standard Development Organizations Universities & research institutes 800+ community size 100 active contributors 250 white paper pages 10 / 2 months / paper releases The OCP Power Distribution sub-project

p8

Interoperability Standards LOWER INTEGRATION RISK Earthing Connectors Control Inter- Generation Compatibility SAFEGUARDING INVESTMENTS COMMON FRAMEWORK 1.0 1.1 2.0 Voltage bands

p9

Safety by Design, Standardized Industry-proven protection for direct current interruption  DC is not new: Solar, Batteries, Electric Vehicles, Ships have deployed DC architectures  Different short-circuit behavior  New standards (e.g. IEC 60947-10 & UL 489I)  Typically, much lower fault energy  DC as safe as AC

p10

• Challenges & Opportunities ahead… o Develop Base System Specification o Develop Base Components Specifications o Continue Codes & Standards work o Engage new stakeholders o Join the Power Distribution community • Direct Current power distribution: o Industry-proven o Resilient & efficient o Safe o Whitepaper #1 most clicked contribution in OCP Path to more power Looking Ahead