PDF 原檔:報告_OCP2026_AdvancedEnergy_800V直供伺服器與電源櫃_20261015_original.pdf
講者公開簡報(OCP 官方 Recorded Content 頁提供下載)。文字以 PyMuPDF 逐頁抽取,
### p<n>為頁碼;圖表內容見原檔。
圖片清單(已驗證 2026-10-19)
| 檔名 | 頁 | 分類 | 親眼所見內容 |
|---|---|---|---|
報告_OCP2026_AdvancedEnergy_800V直供伺服器與電源櫃_20261015_p3.png |
p3 | 真資料圖 | LVDC 關鍵架構圖:HVDC 輸入經 800V 轉 50V shelf(可掛 800V BBU/CBU shelf),或經熱插拔控制器 HSC 與 800V 轉 50V 隔離 DC/DC 進伺服器,再 50V 轉 12V/6V 供 xPU、風扇、儲存 |
報告_OCP2026_AdvancedEnergy_800V直供伺服器與電源櫃_20261015_p9.png |
p9 | 真資料圖 | 160kW 與 100kW power shelf 規格表:皆採 18kW PSU,輸入 HVDC 6 針連接器 4 組(160kW,4×62.5A)對 2 組(100kW),輸出 BK5000(4kA)對 BK2000 bolted 連接器,尺寸 855×46×1086mm 對 537×46×867mm |
報告_OCP2026_AdvancedEnergy_800V直供伺服器與電源櫃_20261015_p10.png |
p10 | 真資料圖 | Option 2 PDB 實板照:熱插拔控制器(HSC)、800V 轉 50V 隔離 DC/DC(>98%)、50V 轉 12V NIBC 磚,板上可見保持電容與濾波器 |
報告_OCP2026_AdvancedEnergy_800V直供伺服器與電源櫃_20261015_p16.png |
p16 | 真資料圖 | AE 樣品與量產品清單:12kW HSC 模組、ADH 系列 4kW/6kW 50V 與 3kW 12V 隔離模組、非隔離 bus converter(900W/1300W/1600W/>2500W)、100kW 與 160kW LVDC shelf、電源管理控制器 PMC,皆標 Sampling |
原始內容
p1
Harry Soin, Senior Director, Advanced Energy Andy Brown, Senior Director, Advanced Energy LVDC direct-to-server and power shelf Challenges and solutions
p2
• Power conversion in LVDC • LVDC – maximize the benefits • LVDC – Challenges to overcome • LVDC Power conversion • Rack mounted solutions • Board mounted solutions • LVDC Board mounted conversion challenges and proposed resolution • Call to action Agenda Items
p3
LVDC – Key architectures • 50V : 12V Non-isolated DCDC • LVDC:50V Isolated DCDC • 50V : 12V Non-isolated DCDC • LVDC in/out Hot-swap controller
p4
• The Motivating factors behind LVDC distribution are well know and documented and is a key enabler to achieve the power- delivery required for next-gen IT racks. • The task is to convert the LVDC to <1V with voltage- conversion steps along the way. The questions are • Where should those voltage-conversion steps happen? • What are the voltage levels that should be used? • The ‘deeper’ the LVDC goes (closer to xPU device), the more benefit is realized. • “deep” means does it remain at the connection point of the equipment or penetrate further into the rack-mounted equipment • The trade-off is that LVDC is more challenging to accommodate the “deeper” it goes into the equipment. LVDC - Distribution and benefits LVDC LVDC : <50V xPU LVDC xPU LVDC/<50V Isolation Isolation <50V distance <50V distance Minimized LVDC distance High-current related losses - Distribution - Connectivity High-current related losses minimized
p5
• SAFETY • The biggest and most challenging aspect is inherently safe power conversion • Isolation/Insulation does not just apply to cables, bus-bars and connectors • For power-Conversion it applies to • Input-to–output, Input-to-ground and output to ground. • “LVDC” has been adopted by the community to relate to +/-400Vdc or 800Vdc • From the Safety Standards, Low Voltage (LV) is only voltage LESS than 60Vdc; Typically known as ELV or SELV • Voltages that exceed 60Vdc are, by definition HAZARDOUS • WHO are we protecting • Installers, Production Operators and maintenance staff • Production staff of the equipment. Challenges to overcome 5 • Layouts to follow • IEC62368 • IEC60664 • IPC-2221B
p6
• What about EMI? (THE most common question asked today) • EMI must be considered if the voltage supplies to more than one piece of equipment, and becomes more important with more equipment • 50V systems have been historically limited to how many pieces of equipment supplied over short distances (within 1 IT rack) – Effects of EMI not “so” critical. • Switching frequencies now exceeding 1MHz = lowest conducted-EMI noise limits • Conducted EMI (Rack and BMP) • Particularly important for Scaling Multiple cabinet connections • Radiated EMI (BMP). • Particularly important when deploying BMP power conversion in close proximity to target devices. Challenges to overcome 6
p7
• Distribution current. • The Lower voltages; keeping the distance that they are supplied as small as possible means less losses and less parasitic effects. • Choosing the right power-conversion steps with corresponding output current is critical for success. • Cooling. • General statement; power conversion architectures are transitioning toward fluid- cooling • Leakage is a tangible reality, and leaking fluid is not desired. Challenges to overcome
p8
• Option 1 - Rack-mounted • Mt Diablo ( 3 Phase AC to 800V or +/-400V) • Down Conversion ( 800V & +/-400V to 50V) • Can take the advantages of LVDC distribution in the rack • Smaller connectors, cables and bus-bars • Lower conduction losses. • Down conversion Options • LVDC to 50V • The 100KW Power Shelf • The 160KW Power Shelf. LVDC Solutions
p9
Rack mounted power solutions 9 160KW Power Shelf 100kW Power Shelf PSU Rating 18KW 18kW Input Cable 4x HVDC 6 pin connectors: +400V, -400V, Return, Earth, Sense1 and Sense2 I/P Current : 4x62.5A 2x HVDC 6 pin connectors: +400V, -400V, Return, Earth, Sense1 and Sense2 Shelf output connector Bolted, BK5000 28mm thick : 4kA Bolted, BK2000 Shelf output connector temp monitoring Yes, with thermistor Yes, with thermistor External busbar temp monitoring Yes, with sensing circuit Yes, with sensing circuit Shelf (W x H x D) 855mm x 46mm x 1086mm 537mm x 46mm x 867mm PSU (W x H x D) 83.4mm x 40mm x 680mm 83.4mm x 40mm x 690mm 100kW and 160kW both uses 18kW PSU, Same PMM as HPRv2 160kW 100kW
p10
LVDC Solutions 10 Hot Swap Controller Active inrush and discharge with Discharge Digital Monitoring Auxiliary Output. Power Distribution Board The integration of the building blocks Safety approved, Electrically characterized, EMI-proven. Includes the hold-up capacitance Fusing and digital control Accelerated development speed! 800V to 50V DCDC modules. At >98% efficiency Isolated, non-regulated NIBC 12Vout Bricks 50V connection and systems Regulated 12V needed with current-sharing Option 2 - PDB
p11
• Isolated DCDC Power conversion density now exceeding 2000W/in3 • Designs have to provide significant Isolation and Insulation distances. • We have large components to accommodate • Hold-up capacitors • Connectors • EMI filters • Fuses • Other bus voltage • Voltage-transients, short-drop-out of input etc Challenges 11 Hold-up caps are large proportional to time, but will have in-rush to manage Multi-stage EMI filter needed due to power demand and switching frequency Large or many-way connectors required for <50V Large fuses and connector for LVDC rating
p12
• Input and output voltage is the LVDC • Standard ½ brick size • Controls the INRUSH current caused by the hold-up capacitors on hot-plug of the rack-mounted equipment • Controls the DISCHARGE of the hold-up capacitors on hot-extraction of the rack-mounted equipment • Integrated PTC to support these functions • Provides ISOLATED 12V Auxiliary output for house keeping circuity on the PDB assembly • Provides digital control and monitoring • IDEAL point to monitor and report input voltage and current. • The Unit must be fully thermally managed for fluid-cooled baseplate attachment Hot Swap Controller
p13
• The DC-DC conversion needs to be Specified as • Power-rated to be convenient building blocks • Standard size, ½ bricks for easy and flexible integration • Input voltage to accommodate all LVDC variations • Output voltage current are 50V or 12V variants. • Reinforced Insulation needed for safety • Isolated for safety • Un-regulated as the LVDC is tightly controlled • High efficiency, >98% efficiency is a must-have • Contact-cooled to fluid-cooled baseplate • Digital control and monitored LVDC input to 50V DCDC BMP • Thermally optimized design for baseplate to be thermally bonded to fluid- cooled cold-plates
p14
50Vin to 12V BMP • Re-use of existing platforms used in 50V systems • Non-Isolated (ELV input, ELV output) • Regulated required for 12V down-stream use. • Standard ¼ brick modules • Optimized for fluid cooled baseplates • Highly efficient, 98% • Many different power levels available • 900W • 1300W • 1600W • >2500W • Thermally optimized design for baseplate to be thermally bonded to fluid-cooled cold-plates
p15
• Safety approved sub-assembly • Cooling, thermally optimized and characterized • Power density optimized for DCDC • Fast Time To Market – using Scalable standard building blocks • Control and monitoring – using digital controlled units Challenges Overcome using a PDB sub-assembly. • EMI; Conducted and Radiated. Characterized and approved • Hold-up function sized for the application requirement • Inrush limiting sized for the in-rush • Active-discharging for safe handling of equipment. • Customized packaging of modular building blocks
p16
AE’s Prototype and Production units LVDC 100KW Power Shelf LVDC 160KW Power Shelf Power Management Controllers Sampling Sampling Sampling • 4KW 50V • 6KW 50V • 3KW 12V HSC module LVDC ; <60Vdc Non Isolated Bus Converters • 900W • 1300W • 1600W • >2500W • 12KW • LVDC-in, LVDC-out Sampling Sampling Sampling
p17
• Get involved in the Rack and Power Project/Sub-Project Community! • Is there a need for a standardized OCP compliant PDB? • Involvement within the community is key for the success of next generation power specifications. • Defining individual requirements are key to creating an overall industry specification. • Project Wiki with latest specification : https://www.opencompute.org/wiki/Open_Rack/SpecsAndDesigns • Mailing list: https://www.opencompute.org/projects/rack-and-power Call to Action
p18