Stock LLM Wiki

報告_OCP2026_Solidigm_單相浸沒SSD驗證_20261015

PDF 原檔:報告_OCP2026_Solidigm_單相浸沒SSD驗證_20261015_original.pdf

講者公開簡報(OCP 官方 Recorded Content 頁提供下載)。文字以 PyMuPDF 逐頁抽取,### p<n> 為頁碼;圖表內容見原檔。

圖片清單(已驗證 2026-10-15)

檔名 頁 分類 親眼所見內容
報告_OCP2026_Solidigm_單相浸沒SSD驗證_20261015_p7.png p7 真資料圖 SSD 專用浸沒平台俯視/等角/側視圖:12×4 SSD 陣列、鋁框、泵浦、流體出入口
報告_OCP2026_Solidigm_單相浸沒SSD驗證_20261015_p8.png p8 真資料圖 SSD 浸沒平台架構圖:介電迴路(測試槽、過濾、流通式加熱器、板式熱交換器、流量計、感測歧管)與冷卻水迴路(液對氣熱交換器、膨脹槽、泵)

原始內容

p1

Jason Brand Thermal Validation Engineer, Solidigm Inc. Justin Boldrini Thermal Validation Engineer, Solidigm Inc. A Practical Framework for SSD Qualification in Single-Phase Immersion Cooling Cooling Environments Immersion Project

p2

SSD Thermochemical Reliability Methodology Pre-immersion • BOM assessment • FMEA development • Baseline performance and functionality • Initial fluid analysis • Weight and dimensions • Component compatibility tests Immersion • Aging Phase: elevated temperature, powered- on idle operation • Readout Phase: Periodic functionality assessment at nominal fluid temperature • Fluid health monitoring Post Immersion • Performance characterization • Thermal validation • Fluid analysis • Weight and dimensions • SI testing • Mechanical reliability testing • Refine FMEA RPNs based on aging results Tear Down • Components material integrity • Cross-section to check PCB, traces, vias • Material residue check This methodology combines elevated-temperature aging, periodic functional verification, and fluid analysis to evaluate the thermochemical aging behavior of SSDs in single-phase immersion environments.

p3

SSD Thermochemical Reliability Methodology Immersion Test Parameters Parameter Aging Phase Readout Phase Fluid Temperature Elevated (e.g., >60°C) Nominal (30-40°C) SSD State Powered-On Idle Powered-On Workload None Functional & Performance Tests Duration Long-term Exposure Periodic Readout Intervals Fluid Monitoring Continuous / Periodic Sampling Continued Monitoring Primary Objective Accelerate Thermochemical Aging Verify Functionality & Performance

p4

• Deployment Environment - Large tanks • Edge Environment • Experimental Immersion • Component Level Tank Immersion Tank Landscape Where do we test SSD form factors in isolation?

p5

Deployment environments and accelerated aging environments have different objectives. Why not use Deployment Environment? Deployment Environment SSD Thermochemical Reliability Testing Environment Designed to maximize system performance and cooling efficiency Designed to accelerate thermochemical aging mechanisms through controlled elevated-temperature exposure Operates near customer operating temperatures Requires elevated temperatures to accelerate thermochemical interactions and degradation mechanisms Multiple components contribute materials and contamination sources Controlled BOM simplifies assessment of materials-fluid interactions Difficult to isolate SSD-specific effects SSD-only testing enables assessment of SSD-specific thermochemical aging effects Larger volumes of fluid Smaller fluid volumes support operational ease while maintaining sufficient volume for fluid aging analysis

p6

Design Goal Develop a dedicated SSD-only immersion platform capable of supporting accelerated thermochemical reliability evaluation while reducing the cost and complexity of full-system immersion infrastructure. Resulting Design Need A dedicated SSD-only immersion platform rather than a conventional deployment tank From Testing Challenges to Design Requirements Key Requirements Support elevated temperature operation (up to ~80°C) Maintain sufficient sample size of SSDs in a powered-on state during aging Enable periodic functional and performance assessments Support fluid property and chemistry analysis Control wetted materials and contamination sources Minimize fluid volume while maintaining sample density

p7

SSD Immersion Platform 12 x 4 SSD Array Pump Aluminum Frame Fluid Outlet Fluid Return Side-view Isometric-view Top-view

p8

SSD Immersion Platform Architecture A B C D E G H I CHILLER LOOP A. Immersion Test Tank B. Filtration Assembly C. Flow-Through Heater D. Plate Heat Exchanger (primary side) E. Flow Meter F. Sensor Manifold D. Plate Heat Exchanger (secondary side) G. Liquid to Air Heat Exchanger H. Expansion Tank I. Pump DIELECTRIC LOOP F

p9

SSD Immersion Platform Architecture A B C D E G H I CHILLER LOOP A. Immersion Test Tank B. Filtration Assembly C. Flow-Through Heater D. Plate Heat Exchanger (primary side) E. Flow Meter F. Sensor Manifold D. Plate Heat Exchanger (secondary side) G. Liquid to Air Heat Exchanger H. Expansion Tank I. Pump DIELECTRIC LOOP F

p10

SSD Immersion Platform Architecture A B C D E G H I CHILLER LOOP A. Immersion Test Tank B. Filtration Assembly C. Flow-Through Heater D. Plate Heat Exchanger (primary side) E. Flow Meter F. Sensor Manifold D. Plate Heat Exchanger (secondary side) G. Liquid to Air Heat Exchanger H. Expansion Tank I. Pump DIELECTRIC LOOP F

p11

Design Goal Develop a dedicated SSD-only immersion platform capable of supporting accelerated thermochemical reliability evaluation while reducing the cost and complexity of full-system immersion infrastructure. Resulting Design Need A dedicated SSD-only immersion platform rather than a conventional deployment tank From Testing Challenges to Design Requirements Key Requirements Support elevated temperature operation (up to ~80°C) Achieved Maintain sufficient sample size of SSDs in a powered-on state during aging Achieved Enable periodic functional and performance assessments Achieved Support fluid property and chemistry analysis Achieved Control wetted materials and contamination sources Achieved Minimize fluid volume while maintaining sample density Achieved

p12

Call to Action: Join the Thermochemical Reliability Workstream • Advance component qualification for immersion cooling environments • Share reliability data, test methodologies, and qualification criteria • Benchmark approaches and learnings across the industry • Collaborate on common qualification frameworks for components in immersion • Help address the challenge of qualifying components across diverse fluids, tank designs, and deployment conditions Call to Action

p13

Thank You!